AAC-All Aluminum Conductor
Applications
All Aluminum Conductors are used in overhead electric power transmission and distribution lines with various grad voltages.
Construction
Aluminum wires are concentrically tranded.
Standrards
All Aluminum Conductors meet or exceed the follwing standards:
IEC 61089, BS 215 part1, DIN 48201 part5, ASTM B231, BS EN50182, GB/T 1179-2008
Area | Num ber of Wires |
Diameter | Linear Mass |
Rated strength |
Max. D. C. Resistance at 20 degree |
|
Wire | Cond | |||||
mm 2 | mm | mm | kg/km | kN | Ω /km | |
10 | 7 | 1.35 | 4.05 | 27.4 | 1.95 | 2.8633 |
16 | 7 | 1.71 | 5.12 | 43.8 | 3.04 | 1.7896 |
25 | 7 | 2.13 | 6.4 | 68.4 | 4.5 | 1.1453 |
40 | 7 | 2.7 | 8.09 | 109.4 | 6.8 | 0.7158 |
63 | 7 | 3.39 | 10.2 | 172.3 | 10.39 | 0.4545 |
100 | 19 | 2.59 | 12.9 | 274.8 | 17.00 | 0.2877 |
125 | 19 | 2.89 | 14.5 | 343.6 | 21.25 | 0.2302 |
160 | 19 | 3.27 | 16.4 | 439.8 | 26.40 | 0.1798 |
200 | 19 | 3.66 | 18.3 | 549.7 | 32.00 | 0.1439 |
250 | 19 | 4.09 | 20.5 | 687.1 | 40.00 | 0.1151 |
315 | 37 | 3.29 | 23.0 | 867.9 | 51.97 | 0.0916 |
400 | 37 | 3.71 | 26.0 | 1102.0 | 64.00 | 0.0721 |
450 | 37 | 3.94 | 27.5 | 1239.8 | 72.00 | 0.0641 |
500 | 37 | 4.15 | 29.0 | 1377.6 | 80.00 | 0.0577 |
560 | 37 | 4.39 | 30.7 | 1542.9 | 89.60 | 0.0515 |
630 | 61 | 3.63 | 32.6 | 1738.3 | 100.80 | 0.0458 |
710 | 61 | 3.85 | 34.6 | 1959.1 | 113.60 | 0.0407 |
800 | 61 | 4.09 | 36.8 | 2207.4 | 128.00 | 0.0361 |
900 | 61 | 4.33 | 39.0 | 2483.3 | 144.00 | 0.0321 |
1000 | 61 | 4.57 | 41.1 | 2759.2 | 160.00 | 0.0289 |
1120 | 91 | 3.96 | 43.5 | 3093.5 | 179.20 | 0.0258 |
1250 | 91 | 4.18 | 46.0 | 3452.6 | 200.00 | 0.0231 |
1400 | 91 | 4.43 | 48.7 | 3866.9 | 224.00 | 0.0207 |
1500 | 91 | 4.58 | 50.4 | 4143.1 | 240.00 | 0.0193 |